← All Advisories
Reported from OT-Advisories.com as of

Siemens APOGEE and TALON Building Controllers Web Service Integer Underflow in Length Validation Lets Unauthenticated Attackers Read Device Memory or Cause Denial of Service

Last refreshed2026-11-16

Status: UPDATED  |  Advisory ID: CVE-2026-102073

Key Details

CVECVE-2026-102073
CVSS Score / Version
8.2 (High) / CVSS v3.1
Updated2026-10-13
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:L
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is none; availability impact is low.
Affected products
see table below
Classified as
CWE-191 (Integer Underflow (Wrap or Wraparound))
Exploitation prediction (EPSS)
0.34% probability of exploitation in the next 30 days (29% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
SiemensAPOGEE MBC (PPC) (BACnet)
SiemensAPOGEE MBC (PPC) (P2 Ethernet)
SiemensAPOGEE MEC (PPC) (BACnet)
SiemensAPOGEE MEC (PPC) (P2 Ethernet)
SiemensAPOGEE PXC Compact (BACnet)
SiemensAPOGEE PXC Compact (P2 Ethernet)
SiemensAPOGEE PXC Modular (BACnet)
SiemensAPOGEE PXC Modular (P2 Ethernet)
SiemensTALON TC Compact (BACnet)
SiemensTALON TC Modular (BACnet)
SubsystemsBuilding Automation & Environmental Controls
SectorsMultiple

What to Know

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The affected product web service does not properly validate the length of user-controllable input. This could allow an unauthenticated remote attacker to read portions of device memory or to cause a denial-of-service condition. (NVD)

What to Do

Disable the FTP/Web service (Note that the FTP/Web service is disabled by default on APOGEE, Desigo, and TALON products.)
Source: Siemens SSA-333035

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-102073
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-102073
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-333035.html
Report compilation © 2026 OT-Advisories.com  ·  CC BY 4.0  ·  Source materials remain the property of their respective publishers as cited.