Siemens APOGEE and TALON Building Controllers Web Service Does Not Validate Upload Code Input Length, Allowing Unauthenticated Denial of Service

Last refreshed2026-11-16

Status: UPDATED  |  Advisory ID: CVE-2026-102076

Key Details

CVECVE-2026-102076
CVSS Score / Version
7.5 (High) / CVSS v3.1
Updated2026-10-13
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is none; integrity impact is none; availability impact is high.
Affected products
see table below
Classified as
CWE-121 (Stack-based Buffer Overflow)
Exploitation prediction (EPSS)
0.42% probability of exploitation in the next 30 days (37% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
SiemensAPOGEE MBC (PPC) (BACnet)
SiemensAPOGEE MBC (PPC) (P2 Ethernet)
SiemensAPOGEE MEC (PPC) (BACnet)
SiemensAPOGEE MEC (PPC) (P2 Ethernet)
SiemensAPOGEE PXC Compact (BACnet)
SiemensAPOGEE PXC Compact (P2 Ethernet)
SiemensAPOGEE PXC Modular (BACnet)
SiemensAPOGEE PXC Modular (P2 Ethernet)
SiemensTALON TC Compact (BACnet)
SiemensTALON TC Modular (BACnet)
SubsystemsBuilding Automation & Environmental Controls
SectorsMultiple

What to Know

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The affected product web service does not properly validate user-supplied input in upload code. This could allow an unauthenticated remote attacker to cause a denial of service. (NVD)

What to Do

CVE-2026-102076 Disable the FTP/Web service (Note that the FTP/Web service is disabled by default on APOGEE, Desigo, and TALON products.)
Source: Siemens SSA-333035

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-102076
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-102076
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-333035.html