Status: UPDATED | Advisory ID: CVE-2026-12819
| CVE | CVE-2026-12819 |
| CVSS Score / Version | |
| Updated | 2026-10-25 |
| Affected products | |
| Classified as | |
| Exploitation prediction (EPSS) |
| Vendor | Product | Affected Versions | Patch Status |
|---|---|---|---|
| deltaww | DVP-12SE |
| Subsystems | General OT |
| Sectors | Multiple |
Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions.
CVE-2026-12819 (CWE-306 Missing Authentication for Critical Function), CVSS 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H. Affected Product: DVP12SE, ALL versions. Corrected: No. Workaround: Users are recommended to take the following mitigation measures: Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access. Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with. Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.
Source: Delta Electronics