← All Advisories
Reported from OT-Advisories.com as of

Linux Kernel H.323 Conntrack DecodeQ931 Reads Past Zero-Length UserUserIE Field on Siemens SIMATIC S7-1500 MFP

Last refreshed2026-11-20

Status: UPDATED  |  Advisory ID: CVE-2026-23455

Key Details

CVECVE-2026-23455
CVSS Score / Version
9.1 (Critical) / CVSS v3.1
Updated2026-11-10
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is none; availability impact is high.
Affected products
see table below
Classified as
CWE-125 (Out-of-bounds Read)
Exploitation prediction (EPSS)
1.62% probability of exploitation in the next 30 days (77% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
LinuxLinux Kernel
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0)
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0)
SubsystemsControllers & Field I/O, OT Supporting Infrastructure
SectorsAll Sectors

What to Know

In the Linux kernel, the following vulnerability has been resolved:

netfilter: nf_conntrack_h323: check for zero length in DecodeQ931()

In DecodeQ931(), the UserUserIE code path reads a 16-bit length from

the packet, then decrements it by 1 to skip the protocol discriminator

byte before passing it to DecodeH323_UserInformation(). If the encoded

length is 0, the decrement wraps to -1, which is then passed as a

large value to the decoder, leading to an out-of-bounds read.

Add a check to ensure len is positive after the decrement. (NVD)

What to Do

Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Only build and run applications from trusted sources. Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only.
Source: Siemens SSA-082556

2 other advisories state the same guidance
  • Currently no fix is available
    Source: Siemens SSA-019113
  • Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only. Only build and run applications from trusted sources.
    Source: Siemens SSA-457936

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-23455
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-23455
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-019113.html
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-082556.html
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-457936.html
Report compilation © 2026 OT-Advisories.com  ·  CC BY 4.0  ·  Source materials remain the property of their respective publishers as cited.