Status: UPDATED | Advisory ID: CVE-2026-23457
| CVE | CVE-2026-23457 |
| CVSS Score / Version | |
| Updated | 2026-11-10 |
| CVSS Vector | |
| CVSS Prose | |
| Affected products | |
| Classified as | |
| Exploitation prediction (EPSS) |
| Vendor | Product | Affected Versions | Patch Status |
|---|---|---|---|
| Linux | Linux Kernel | ||
| Siemens | SIMATIC S7-1500 CPU 1518-4 PN/DP MFP | ||
| Siemens | SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP | ||
| Siemens | SIPLUS S7-1500 CPU 1518-4 PN/DP MFP | ||
| Siemens | SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0) | ||
| Siemens | SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0) | ||
| Siemens | SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0) | ||
| Siemens | SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0) | ||
| Siemens | SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0) |
| Subsystems | Controllers & Field I/O, OT Supporting Infrastructure |
| Sectors | All Sectors |
In the Linux kernel, the following vulnerability has been resolved:
netfilter: nf_conntrack_sip: fix Content-Length u32 truncation in sip_help_tcp()
sip_help_tcp() parses the SIP Content-Length header with
simple_strtoul(), which returns unsigned long, but stores the result in
unsigned int clen. On 64-bit systems, values exceeding UINT_MAX are
silently truncated before computing the SIP message boundary.
For example, Content-Length 4294967328 (2^32 + 32) is truncated to 32,
causing the parser to miscalculate where the current message ends. The
loop then treats trailing data in the TCP segment as a second SIP
message and processes it through the SDP parser.
Fix this by changing clen to unsigned long to match the return type of
simple_strtoul(), and reject Content-Length values that exceed the
remaining TCP payload length. (NVD)
Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Only build and run applications from trusted sources. Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only.
Source: Siemens SSA-0825562 other advisories state the same guidance
Source: Siemens SSA-019113
Source: Siemens SSA-457936