← All Advisories
Reported from OT-Advisories.com as of

Unauthenticated Path Traversal in Pepperl+Fuchs ICE-Series IO-Link Masters Exposes the Device's SSH Server Private Keys

Last refreshed2026-11-17

Status: UPDATED  |  Advisory ID: CVE-2026-27557

Key Details

CVECVE-2026-27557
CVSS Score / Version
7.5 (High) / CVSS v3.1
Updated2026-09-16
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is none; availability impact is none.
Affected products
see table below
Classified as
CWE-35 (Path Traversal: '.../...//')
Exploitation prediction (EPSS)
0.71% probability of exploitation in the next 30 days (54% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
Pepperl+FuchsICE2-8IOL-K45P-RJ45
Pepperl+FuchsICE2-8IOL1-G65L-V1D
Pepperl+FuchsICE2-8IOL-G65L-V1D
Pepperl+FuchsICE2-8IOL-K45S-RJ45
Pepperl+FuchsICE3-8IOL1-G65L-V1D
Pepperl+FuchsICE3-8IOL-G65L-V1D
Pepperl+FuchsICE3-8IOL-G65L-V1D-Y
Pepperl+FuchsICE3-8IOL-K45P-RJ45
Pepperl+FuchsICE3-8IOL-K45S-RJ45
Phoenix ContactIOL MA8 PN DI8
Phoenix ContactIOL MA8 EIP DI8
Carlo Gavazzi AutomationYL212CEI8M1IO
Carlo Gavazzi AutomationYN115CEI8RPIO
Carlo Gavazzi AutomationYL212CPN8M1IO
Carlo Gavazzi AutomationYN115CPN8RPIO
SubsystemsAutomation / MES, Controllers & Field I/O
SectorsMultiple

What to Know

An unauthenticated remote attacker can exploit a path traversal vulnerability in the /index.php/view_uploaded_iodd_file endpoint allowing the SSH server's private keys to be read.

What to Do

CVE-2026-27557: Path Traversal: '.../...//' (CWE-35). Summary: An unauthenticated remote attacker can exploit a path traversal vulnerability in the /index.php/view_uploaded_iodd_file endpoint allowing the SSH server's private keys to be read. Affected Product(s): Pepperl+Fuchs ICE2-*/ICE3-* IO-Link Masters, Firmware < 1.7.4. Mitigation: Minimize network exposure for affected products and ensure that they are not accessible via the Internet. Isolate affected products from the corporate network. If remote access is required, use secure methods such as virtual private networks (VPNs). Remediation: Install the firmware update 1.7.8.
Source: Pepperl+Fuchs SE (via CERT@VDE) VDE-2026-014

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-27557
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-27557
Vendor advisoryhttps://www.certvde.com/en/advisories/VDE-2026-014/
Vendor advisoryhttps://www.certvde.com/en/advisories/VDE-2026-027/
Vendor advisoryhttps://www.certvde.com/en/advisories/VDE-2026-028/