← All Advisories

Admin-Level PUT Requests to the IODD Configuration API Execute Injected Commands as Root on Pepperl+Fuchs ICE-Series IO-Link Masters

Last refreshed2026-09-30

Status: UPDATED  |  Advisory ID: CVE-2026-27562

Key Details

CVECVE-2026-27562
CVSS Score / Version7.2 (High) / CVSS v3.1
Updated2026-09-16
CVSS VectorCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H
CVSS Proseattack vector is network; attack complexity is low; privileges required is high; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is high; availability impact is high.
Affected productssee table below
Classified asCWE-78 (Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection'))

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
Pepperl+FuchsICE2-8IOL-K45P-RJ45
Pepperl+FuchsICE2-8IOL1-G65L-V1D
Pepperl+FuchsICE2-8IOL-G65L-V1D
Pepperl+FuchsICE2-8IOL-K45S-RJ45
Pepperl+FuchsICE3-8IOL1-G65L-V1D
Pepperl+FuchsICE3-8IOL-G65L-V1D
Pepperl+FuchsICE3-8IOL-G65L-V1D-Y
Pepperl+FuchsICE3-8IOL-K45P-RJ45
Pepperl+FuchsICE3-8IOL-K45S-RJ45
Phoenix ContactIOL MA8 PN DI8
Phoenix ContactIOL MA8 EIP DI8
Carlo Gavazzi AutomationYL212CEI8M1IO
Carlo Gavazzi AutomationYN115CEI8RPIO
Carlo Gavazzi AutomationYL212CPN8M1IO
Carlo Gavazzi AutomationYN115CPN8RPIO
SubsystemsGeneral OT
SectorsMultiple

What to Know

A high-privileged remote attacker can exploit a command injection vulnerability in the /api/iodd/config endpoint by sending a crafted PUT request with admin credentials allowing execution of commands with root privileges on the device.

What to Do

Monitor Pepperl+Fuchs, Phoenix Contact, and Carlo Gavazzi Automation's web pages for any future patch releases.

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-27562
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-27562