← All Advisories
Reported from OT-Advisories.com as of

Nozomi Networks Guardian Arc Sensor Sync Incorrectly Grants CLI Permissions to Low-Privileged Authenticated Users

Last refreshed2026-11-16

Status: UPDATED  |  Advisory ID: CVE-2026-33390

Key Details

CVECVE-2026-33390
CVSS Score / Version
8.1 (High) / CVSS v3.1
Updated2026-08-11
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is low; user interaction is none; scope is unchanged; confidentiality impact is none; integrity impact is high; availability impact is high.
Affected products
Nozomi Networks Guardian, Nozomi Networks CMC, and Siemens RUGGEDCOM APE1808
Classified as
CWE-266 (Incorrect Privilege Assignment)
Exploitation prediction (EPSS)
0.40% probability of exploitation in the next 30 days (35% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
Nozomi NetworksGuardian
Nozomi NetworksCMC
SiemensRUGGEDCOM APE1808
SubsystemsIndustrial Networking & Connectivity
SectorsMultiple

What to Know

An Incorrect Privilege Assignment vulnerability was discovered in the synchronization functionality due to Arc sensors receiving CLI permissions. An authenticated user with limited privileges can push administrative CLI commands through the sync, altering the device configuration, and/or affecting its availability. (NVD)

What to Do

Workarounds and Mitigations: Review all enabled sensors and disallow or delete untrusted ones. Solutions: Upgrade to v26.2.0 or later.
Source: Nozomi Networks NN-2026:13-01

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-33390
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-33390
Vendor advisoryhttps://security.nozominetworks.com/NN-2026:13-01
Report compilation © 2026 OT-Advisories.com  ·  CC BY 4.0  ·  Source materials remain the property of their respective publishers as cited.