Linux Kernel IPv6 NDISC Router Advertisement User Option Leaves Padding Fields Uninitialized on Siemens SIMATIC S7-1500 MFP

Last refreshed2026-11-17

Status: UPDATED  |  Advisory ID: CVE-2026-43040

Key Details

CVECVE-2026-43040
CVSS Score / Version
7.1 (High) / CVSS v3.1
Updated2026-11-10
CVSS Vector
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:H
CVSS Prose
attack vector is local; attack complexity is low; privileges required is low; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is none; availability impact is high.
Affected products
see table below
Classified as
CWE-909 (Missing Initialization of Resource)
Exploitation prediction (EPSS)
0.13% probability of exploitation in the next 30 days (3% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
LinuxLinux Kernel
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0)
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0)
SubsystemsControllers & Field I/O, OT Supporting Infrastructure
SectorsAll Sectors

What to Know

In the Linux kernel, the following vulnerability has been resolved:

net: ipv6: ndisc: fix ndisc_ra_useropt to initialize nduseropt_padX fields to zero to prevent an info-leak

When processing Router Advertisements with user options the kernel

builds an RTM_NEWNDUSEROPT netlink message. The nduseroptmsg struct

has three padding fields that are never zeroed and can leak kernel data

The fix is simple, just zeroes the padding fields. (NVD)

What to Do

Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Only build and run applications from trusted sources. Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only.
Source: Siemens SSA-082556

2 other advisories state the same guidance
  • Currently no fix is available
    Source: Siemens SSA-019113
  • Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only. Only build and run applications from trusted sources.
    Source: Siemens SSA-457936

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-43040
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-43040
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-019113.html