Phoenix Contact CHARX SEC Firewall Terminated Prematurely During System Shutdown Creates Temporary Window Exposing Internal Services
Last refreshed2026-11-16
Status: UPDATED
| Advisory ID: CVE-2026-44108
Key Details
CVE
CVE-2026-44108
CVSS Score / Version
9.8 (Critical) / CVSS v3.1
Updated
2026-07-30
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is high; availability impact is high.
0.83% probability of exploitation in the next 30 days (58% percentile) -- FIRST.org's EPSS model.
Affected Products, Subsystems & Sectors
Vendor
Product
Affected Versions
Patch Status
Phoenix Contact
CHARX SEC-3150
Phoenix Contact
CHARX SEC-3100
Phoenix Contact
CHARX SEC-3050
Phoenix Contact
CHARX SEC-3000
Subsystems
Distributed Energy & Facility Power Management
Sectors
Multiple
What to Know
Due to a flaw in the execution order of scripts during shutdown, the firewall is terminated prematurely during system shutdown. This creates a temporary window in which internal services may become externally accessible, potentially allowing an unauthenticated remote attacker to connect to these services, resulting in full system compromise. (NVD)
What to Do
Phoenix Contact recommends updating affected devices to firmware version 1.9.1, which addresses these vulnerabilities. The updated firmware will be made available as soon as possible, but no later than August 12, 2026. Please check the download section of the respective product webpage for the availability of the fix. Source: Phoenix Contact VDE-2026-008