← All Advisories
Reported from OT-Advisories.com as of

Linux Kernel IPv4 ICMP Extended Echo Reply Type Not Validated Before Pointer Use on Siemens SIMATIC S7-1500 MFP

Last refreshed2026-11-20

Status: UPDATED  |  Advisory ID: CVE-2026-46037

Key Details

CVECVE-2026-46037
CVSS Score / Version
8.2 (High) / CVSS v3.1
Updated2026-11-10
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is low; integrity impact is none; availability impact is high.
Affected products
see table below
Classified as
CWE-125 (Out-of-bounds Read)
Exploitation prediction (EPSS)
0.51% probability of exploitation in the next 30 days (45% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
LinuxLinux Kernel
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 TM MFP - GNU/Linux subsystem
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0)
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0)
SubsystemsControllers & Field I/O, OT Supporting Infrastructure
SectorsAll Sectors

What to Know

In the Linux kernel, the following vulnerability has been resolved:

ipv4: icmp: validate reply type before using icmp_pointers

Extended echo replies use ICMP_EXT_ECHOREPLY as the outbound reply type.

That value is outside the range covered by icmp_pointers[], which only

describes the traditional ICMP types up to NR_ICMP_TYPES.

Avoid consulting icmp_pointers[] for reply types outside that range, and

use array_index_nospec() for the remaining in-range lookup. Normal ICMP

replies keep their existing behavior unchanged. (NVD)

What to Do

Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only. Only build and run applications from trusted sources.
Source: Siemens SSA-457936

2 other advisories state the same guidance
  • Currently no fix is available
    Source: Siemens SSA-019113
  • Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Only build and run applications from trusted sources. Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only.
    Source: Siemens SSA-784472

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-46037
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-46037
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-019113.html
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-457936.html
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-784472.html
Report compilation © 2026 OT-Advisories.com  ·  CC BY 4.0  ·  Source materials remain the property of their respective publishers as cited.