Status: UPDATED | Advisory ID: CVE-2026-4827
| CVE | CVE-2026-4827 |
| CVSS Score / Version | |
| Updated | 2026-06-17 |
| Affected products | |
| Classified as | |
| Exploitation prediction (EPSS) |
| Vendor | Product | Affected Versions | Patch Status |
|---|---|---|---|
| Schneider Electric | Easergy MiCOM C264 | ||
| Schneider Electric | Easergy C5 | ||
| Schneider Electric | Easergy MiCOM P30 | ||
| Schneider Electric | Easergy MiCOM P40 | ||
| Schneider Electric | EcoStruxure™ Power Automation System Gateway (EPAS-GTW) | ||
| Schneider Electric | EcoStruxure™ Power Automation System User Interface (EPAS-UI) | ||
| Schneider Electric | EcoStruxure™ Power Operation | ||
| Schneider Electric | iPMFLS | ||
| Schneider Electric | PowerLogic™ P5 Protection Relay | ||
| Schneider Electric | PowerLogic™ P7 Protection and Control Platform | ||
| Schneider Electric | PowerLogic™ T300 | ||
| Schneider Electric | PowerLogic™ T500 | ||
| Schneider Electric | Saitel DP | ||
| Schneider Electric | EasyLogic T150 (formerly Saitel DR) |
| Subsystems | Power Systems, Substation & Electrical Distribution Automation |
| Sectors | Multiple |
CWE‑331: Insufficient Entropy vulnerability exists that could lead to unauthorized access when an attacker on the network can exploit weaknesses in session‑management protections.
Remediation: Easergy MiCOM C264 -- Version D7.34 of MiCOM C264 includes a fix for this vulnerability. Easergy C5 -- Version 1.1.18 of Easergy C5 includes a fix for this vulnerability. Easergy MiCOM P30/P40 family (various P1xx/P4xx/P5xx/P6xx models) -- specific fixed firmware versions per model (e.g. P633.680.701, P539.678.700, P634.680.701, P139.678.700, P439.678.700, P138.677.701, C434.679.700, P632.678.700). EasyLogic T150 -- Firmware version 11.06.31. EcoStruxure Power Automation System Gateway -- Version 6.4.610.500.101. EPAS-UI -- Version 3.0.4. EcoStruxure Power Operation -- EPO 2022 CU 7 / EPO 2024 CU 3. iPMFLS -- Version 64.2025.0.14. PowerLogic P5 -- V02.503.101. PowerLogic P7 -- V02.003.001. PowerLogic T300 -- 2.9.5. PowerLogic T500 -- 11.08.03. Saitel DP -- CPU866e Firmware version 11.06.37. Contact Schneider Electric's Customer Care Center for information on how to obtain each fix. If customers choose not to apply the remediation provided above, mitigations are given for a small number of models (certain Easergy MiCOM P30/P40 variants) for which Schneider Electric is still establishing a remediation plan and has not yet released a fix: operate within a physically/logically segmented network behind a firewall/IDS, and reduce the session inactivity timeout.
Source: Schneider Electric