← All Advisories
Reported from OT-Advisories.com as of

Linux Kernel netfilter Conntrack sprintf Usage Risks Buffer Overrun on Siemens SIMATIC S7-1500 MFP

Last refreshed2026-11-17

Status: UPDATED  |  Advisory ID: CVE-2026-53002

Key Details

CVECVE-2026-53002
CVSS Score / Version
9.8 (Critical) / CVSS v3.1
Updated2026-11-10
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is high; availability impact is high.
Affected products
see table below
Classified as
CWE-787 (Out-of-bounds Write)
Exploitation prediction (EPSS)
0.37% probability of exploitation in the next 30 days (31% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
Red HatEnterprise Linux
LinuxLinux Kernel
Red HatRed Hat Enterprise Linux 10
Red HatRed Hat Enterprise Linux 8
Red HatRed Hat Enterprise Linux 9
Red HatRed Hat Enterprise Linux 7
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0)
SiemensSIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0)
SiemensSIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0)
SubsystemsControllers & Field I/O, OT Supporting Infrastructure
SectorsAll Sectors

What to Know

In the Linux kernel, the following vulnerability has been resolved:

netfilter: conntrack: remove sprintf usage

Replace it with scnprintf, the buffer sizes are expected to be large enough

to hold the result, no need for snprintf+overflow check.

Increase buffer size in mangle_content_len() while at it.

BUG: KASAN: stack-out-of-bounds in vsnprintf+0xea5/0x1270

Write of size 1 at addr [..]

vsnprintf+0xea5/0x1270

sprintf+0xb1/0xe0

mangle_content_len+0x1ac/0x280

nf_nat_sdp_session+0x1cc/0x240

process_sdp+0x8f8/0xb80

process_invite_request+0x108/0x2b0

process_sip_msg+0x5da/0xf50

sip_help_tcp+0x45e/0x780

nf_confirm+0x34d/0x990

[..] (NVD)

What to Do

Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only. Only build and run applications from trusted sources.
Source: Siemens SSA-457936

1 other advisory states the same guidance

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-53002
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-53002
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-019113.html
Vendor advisoryhttps://cert-portal.siemens.com/productcert/html/ssa-457936.html
Report compilation © 2026 OT-Advisories.com  ·  CC BY 4.0  ·  Source materials remain the property of their respective publishers as cited.