Status: UPDATED | Advisory ID: CVE-2026-53239
| CVE | CVE-2026-53239 |
| CVSS Score / Version | |
| Updated | 2026-11-10 |
| CVSS Vector | |
| CVSS Prose | |
| Affected products | |
| Classified as | |
| Exploitation prediction (EPSS) |
| Vendor | Product | Affected Versions | Patch Status |
|---|---|---|---|
| Linux | Linux Kernel | ||
| Siemens | SIMATIC S7-1500 CPU 1518-4 PN/DP MFP | ||
| Siemens | SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP | ||
| Siemens | SIPLUS S7-1500 CPU 1518-4 PN/DP MFP | ||
| Siemens | SIMATIC S7-1500 TM MFP - GNU/Linux subsystem | ||
| Siemens | SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0) | ||
| Siemens | SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0) | ||
| Siemens | SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0) | ||
| Siemens | SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0) | ||
| Siemens | SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0) |
| Subsystems | Controllers & Field I/O, OT Supporting Infrastructure |
| Sectors | All Sectors |
In the Linux kernel, the following vulnerability has been resolved:
xfrm: policy: fix use-after-free on inexact bin in xfrm_policy_bysel_ctx()
Fix the race by pruning the bin while still holding xfrm_policy_lock,
before dropping it. Use __xfrm_policy_inexact_prune_bin() directly since
the lock is already held. The wrapper xfrm_policy_inexact_prune_bin()
becomes unused and is removed.
Race:
CPU0 (XFRM_MSG_DELPOLICY) CPU1 (XFRM_MSG_NEWSPDINFO)
========================== ==========================
xfrm_policy_bysel_ctx():
spin_lock_bh(xfrm_policy_lock)
bin = xfrm_policy_inexact_lookup()
__xfrm_policy_unlink(pol)
spin_unlock_bh(xfrm_policy_lock)
xfrm_policy_kill(ret)
// wide window, lock not held
xfrm_hash_rebuild():
spin_lock_bh(xfrm_policy_lock)
__xfrm_policy_inexact_flush():
kfree_rcu(bin) // bin freed
spin_unlock_bh(xfrm_policy_lock)
xfrm_policy_inexact_prune_bin(bin)
// UAF: bin is freed (NVD)
Currently no fix is available. Siemens has identified the following specific mitigations that customers can apply to reduce the risk: Limit access to the interactive shell of the additional GNU/Linux subsystem to trusted personnel only. Only build and run applications from trusted sources.
Source: Siemens SSA-4579362 other advisories state the same guidance
Source: Siemens SSA-019113
Source: Siemens SSA-784472