Siemens SIMATIC S7-PLCSIM Advanced High-Volume Multicast Traffic Exhausts Device Memory, Causing Denial of Service
Last refreshed2026-11-16
Status: UPDATED
| Advisory ID: CVE-2026-54429
Key Details
CVE
CVE-2026-54429
CVSS Score / Version
7.4 (High) / CVSS v3.1
Updated
2026-07-15
CVSS Vector
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H
CVSS Prose
attack vector is adjacent; attack complexity is low; privileges required is none; user interaction is none; scope is changed; confidentiality impact is none; integrity impact is none; availability impact is high.
Affected products
Siemens SIMATIC S7-PLCSIM Advanced
Classified as
CWE-770 (Allocation of Resources Without Limits or Throttling)
Exploitation prediction (EPSS)
0.27% probability of exploitation in the next 30 days (19% percentile) -- FIRST.org's EPSS model.
Affected Products, Subsystems & Sectors
Vendor
Product
Affected Versions
Patch Status
Siemens
SIMATIC S7-PLCSIM Advanced
Subsystems
General OT
Sectors
Multiple
What to Know
A vulnerability has been identified in SIMATIC S7-PLCSIM Advanced (All versions). Affected devices do not properly handle high-volume multicast network traffic, which can exhaust available memory resources in the affected application. This could allow an unauthenticated attacker on the local network segment to cause a denial-of-service condition of the affected application. The affected application becomes inaccessible and requires a manual restart; no project data is lost. Successful exploitation requires a specific project configuration to be already active on the targeted instance. (NVD)
What to Do
SIMATIC S7-PLCSIM Advanced All versions affected by CVE-2026-54429 Currently no fix is available Source: Siemens SSA-828211