Siemens Reyrolle 7SR5 Web Interface Exposes Session ID Calculation Information, Allowing Session Hijacking Without Credentials
Last refreshed2026-11-16
Status: UPDATED
| Advisory ID: CVE-2026-62645
Key Details
CVE
CVE-2026-62645
CVSS Score / Version
9.8 (Critical) / CVSS v3.1
Updated
2026-09-08
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is high; availability impact is high.
Affected products
Siemens Reyrolle 7SR5
Classified as
CWE-306 (Missing Authentication for Critical Function)
Exploitation prediction (EPSS)
0.65% probability of exploitation in the next 30 days (52% percentile) -- FIRST.org's EPSS model.
Affected Products, Subsystems & Sectors
Vendor
Product
Affected Versions
Patch Status
Siemens
Reyrolle 7SR5
Subsystems
Power Systems, Substation & Electrical Distribution Automation
Sectors
Multiple
What to Know
A vulnerability has been identified in Reyrolle 7SR5 (All versions < V2.70). Information is exposed through the web interface that can be used to calculate the current and past session ID numbers. This could allow an attacker to bypass the authentication and gain unauthorized access to the device. (NVD)
What to Do
Reyrolle 7SR5: All versions < V2.70 affected by all CVEs. Update to V2.70 or later version. https://support.industry.siemens.com/cs/ww/en/view/109772413/ Source: Siemens SSA-142885